datacenter

datacenter

Use this skill when the user says 'datacenter', 'data center', 'DC', 'rack', 'power', 'cooling', 'PDU', 'UPS', 'Tier classification', 'N+1 redundancy', '2N redundancy', 'cabling', 'fiber', 'copper', 'hot aisle', 'cold aisle', 'rack density', 'kW per rack', 'DCIM', 'data center operations', 'colocation'. Covers: datacenter tier classification (Tier I-IV), po…

Independent GitHub snapshot · Automated classification · Original documentation governs

Documentation de la Skill

GitHub

name: datacenter description: > Use this skill when the user says 'datacenter', 'data center', 'DC', 'rack', 'power', 'cooling', 'PDU', 'UPS', 'Tier classification', 'N+1 redundancy', '2N redundancy', 'cabling', 'fiber', 'copper', 'hot aisle', 'cold aisle', 'rack density', 'kW per rack', 'DCIM', 'data center operations', 'colocation'. Covers: datacenter tier classification (Tier I-IV), power and cooling design, rack layout, cabling standards, DCIM tools, capacity planning, redundancy models, environmental monitoring, colocation selection. Do NOT use for: cloud infrastructure (use cloud-specific skills), server provisioning (use bare-metal skill). version: "2.0.0" author: "j4flmao" license: "MIT" compatibility: claude-code: true cursor: true codex: true windsurf: true tags: [devops, datacenter, infrastructure, hardware, phase-5]

Datacenter Operations

Purpose

Design, operate, and manage physical datacenter infrastructure including tier classification, power/cooling, rack layout, cabling, DCIM, and capacity planning.

Architecture Decision Trees

Datacenter Tier Classification

TierAvailabilityRedundancyAnnual DowntimeCost Premium
Tier I (Basic)99.671%None (N)28.8 hours1x (baseline)
Tier II (Redundant)99.741%N+1 (power/cooling)22.7 hours1.2-1.5x
Tier III (Concurrently Maintainable)99.982%N+1 (all components)1.6 hours1.8-2.5x
Tier IV (Fault Tolerant)99.995%2N (fully redundant)26.3 minutes3-5x

Power Redundancy Models

ModelDescriptionUPS ConfigGeneratorCost vs N
NSingle path1 UPS1 generator1x
N+1Redundant component2 UPS (N+1)2 generators (N+1)1.3x
2NTwo independent paths2 UPS (each N)2 generators (each N)2x
2N+1Two paths + redundant3 UPS (2N+1)3 generators2.3x

Cooling Architecture Comparison

TypePUE ImpactCapacity (kW/rack)CostBest For
Room-based (CRAC)1.4-1.8<10LowLegacy DCs, low density
Row-based (in-row)1.2-1.410-25MediumStandard deployments
Rack-based (rear door)1.1-1.315-40Medium-HighHigh-density (GPU/HPC)
Liquid (direct-to-chip)1.05-1.140-100+HighHPC, AI/ML clusters
Immersion1.02-1.05100+Very HighExtreme density

Cooling Selection Decision Tree

Average rack density < 10 kW?
├── Yes → Room-based CRAC (PUE 1.4-1.8, lowest cost)
└── No → Average rack density 10-25 kW?
    ├── Yes → Row-based in-row cooling (PUE 1.2-1.4)
    └── No → Average rack density 25-40 kW?
        ├── Yes → Rack-based rear door heat exchanger (PUE 1.1-1.3)
        └── No → > 40 kW?
            ├── Yes → GPU/HPC/AI workloads?
            │   ├── Yes → Liquid direct-to-chip or immersion (PUE < 1.1)
            │   └── No → Evaluate rack-based + supplemental cooling
            └── N/A → Reassess density requirements

Colocation Selection Criteria

FactorRetail ColoWholesale ColoHyperscaler Edge
SpacePer rackPer cage/suitePer cabinet
Contract1-3 years3-10 yearsFlexible
ManagementHands-on supportSelf-managedRemote hands
ConnectivityShared meet-me roomDedicated cross-connectsProvider-specific
Cost/rack/month$1,000-3,000$500-1,500Varies
Power includedOften (up to limit)Separate billingPer circuit
Cross-connectsIncluded or $100-500/moIncludedPer connection
SLA99.9-99.99%99.99%Provider SLA

Redundancy Decision Tree

Is the workload business-critical (revenue-impacting)?
├── Yes → Can we tolerate planned maintenance downtime?
│   ├── Yes → Tier II (N+1, lower cost)
│   └── No → Tier III (N+1, concurrently maintainable)
└── No → Can we tolerate any downtime at all?
    ├── No → Tier IV (2N, fault tolerant, highest cost)
    └── Yes → Tier I (N, lowest cost, best for dev/test)

Core Workflow

Step 1: Rack Layout Design

Standard 42U Rack Layout (Front View)
┌──────────────────────┐
│  [1U] Patch Panel    │ U 1
│  [1U] Patch Panel    │ U 2
│──────────────────────│
│  [2U] Core Switch 1  │ U 3-4
│  [2U] Core Switch 2  │ U 5-6
│──────────────────────│
│  [1U] PDU A (3-phase)│ U 7
│  [1U] PDU B (3-phase)│ U 8
│──────────────────────│
│  [1U] Server 1       │ U 9
│  [1U] Server 2       │ U 10
│  [1U] Server 3       │ U 11
│  [1U] Server 4       │ U 12
│──────────────────────│
│  [2U] Storage Array  │ U 13-14
│──────────────────────│
│  [1U] Server 5       │ U 15
│  [1U] Server 6       │ U 16
│  [1U] Server 7       │ U 17
│  [1U] Server 8       │ U 18
│──────────────────────│
│  [2U] UPS (per rack) │ U 19-20
│──────────────────────│
│  [1U] empty          │ U 21
│  [1U] empty          │ U 22
│  ...                 │ ...
│──────────────────────│
│  [4U] GPU Server     │ U 38-41
│  [1U] BMC Switch     │ U 42
└──────────────────────┘

Power Distribution:
  Feed A: PDU A (A-phase) → Server PSU A
  Feed B: PDU B (B-phase) → Server PSU B
  Each PSU: 120V/208V/240V based on equipment

Cabling:
  Fiber: Patch panel U1 → ToR Switch
  Copper: Patch panel U2 → Server NICs
  Management: BMC ports → BMC switch (U42)

Step 2: Power Capacity Planning

# capacity/power_planning.py
"""Datacenter power capacity planning tool."""

RACK_POWER_MAP = {
    "standard_rack": {
        "servers": 16,          # 1U servers
        "gpu_servers": 1,       # 4U GPU servers
        "switches": 2,          # ToR switches, 2U each
        "storage": 1,           # Storage array, 2U
    },
    "high_density_rack": {
        "servers": 8,
        "gpu_servers": 4,
        "switches": 2,
        "storage": 2,
    },
}

POWER_PER_COMPONENT = {
    "1u_server": {"idle_w": 80, "max_w": 250},
    "gpu_server": {"idle_w": 500, "max_w": 2500},
    "tor_switch": {"idle_w": 150, "max_w": 400},
    "storage_array": {"idle_w": 200, "max_w": 600},
}

def calculate_rack_power(rack_type="standard_rack"):
    """Calculate total power per rack."""
    config = RACK_POWER_MAP[rack_type]
    total_idle = 0
    total_max = 0

    total_idle += config["servers"] * POWER_PER_COMPONENT["1u_server"]["idle_w"]
    total_max += config["servers"] * POWER_PER_COMPONENT["1u_server"]["max_w"]
    total_idle += config["gpu_servers"] * POWER_PER_COMPONENT["gpu_server"]["idle_w"]
    total_max += config["gpu_servers"] * POWER_PER_COMPONENT["gpu_server"]["max_w"]
    total_idle += config["switches"] * POWER_PER_COMPONENT["tor_switch"]["idle_w"]
    total_max += config["switches"] * POWER_PER_COMPONENT["tor_switch"]["max_w"]
    total_idle += config["storage"] * POWER_PER_COMPONENT["storage_array"]["idle_w"]
    total_max += config["storage"] * POWER_PER_COMPONENT["storage_array"]["max_w"]

    return {"idle_kw": total_idle / 1000, "max_kw": total_max / 1000}

def calculate_power_for_room(num_racks, rack_type="standard_rack", redundancy="N"):
    """Calculate total power infrastructure needed."""
    rack_power = calculate_rack_power(rack_type)
    total_it_load = rack_power["max_kw"] * num_racks

    # Cooling overhead
    cooling_factor = 1.3  # Typical PUE for row-cooled DC
    total_facility = total_it_load * cooling_factor

    # Redundancy factor
    redundancy_factors = {
        "N": 1.0,
        "N+1": 1.3,
        "2N": 2.0,
        "2N+1": 2.3,
    }
    total_redundant = total_facility * redundancy_factors[redundancy]

    # UPS capacity
    ups_capacity = total_redundant * 1.2  # 20% headroom

    return {
        "it_load_kw": total_it_load,
        "facility_load_kw": total_facility,
        "redundant_load_kw": total_redundant,
        "ups_capacity_kw": ups_capacity,
        "ups_runtime_min": 15,  # Typical battery runtime
        "generator_kw": total_redundant * 1.1,
    }

# Example: 20 racks, standard density, N+1 redundancy
power = calculate_power_for_room(20, "standard_rack", "N+1")
for k, v in power.items():
    if "kw" in k:
        print(f"{k}: {v:.1f} kW")
    else:
        print(f"{k}: {v}")

Step 3: Cabling Standards

# cabling/cabling-standards.yaml
structured_cabling:
  copper:
    cat6a:  # 10Gbps, 100m max
      use: "Server to ToR, management"
      max_length_m: 100
      termination: "RJ45 (T568B)"
    cat8:  # 25/40Gbps, 30m max
      use: "Switch to switch, high-speed links"
      max_length_m: 30

  fiber:
    om3_multimode:  # 10G-100G, 300m
      use: "ToR to EoR, storage networks"
      max_length_m: 300
      connector: "LC duplex"
    om4_multimode:
      use: "High-speed storage (32G FC)"
      max_length_m: 400
    os2_singlemode:  # 100G-400G+, >10km
      use: "Inter-rack, cross-connect, WAN"
      max_length_m: 40000
      connector: "LC (polished)"

  labeling:
    standard: "TIA-606-B"
    format: "RACK-PANEL-PORT"  # e.g., A01-P01-001
    labels_required:
      - "Both ends of every cable"
      - "Patch panel ports"
      - "Outlet faceplates"
      - "Breakout points"

Step 4: DCIM Integration Script

# dcim/rack_monitor.py
"""Monitor rack-level power, temperature, and humidity via DCIM API."""

import requests
import time
import json
from datetime import datetime

class DCIMClient:
    def __init__(self, base_url, api_token):
        self.base_url = base_url.rstrip('/')
        self.session = requests.Session()
        self.session.headers.update({'Authorization': f'Bearer {api_token}'})

    def get_rack_sensors(self, rack_id):
        resp = self.session.get(f"{self.base_url}/api/racks/{rack_id}/sensors")
        resp.raise_for_status()
        return resp.json()

    def get_pdu_load(self, pdu_id):
        resp = self.session.get(f"{self.base_url}/api/pdus/{pdu_id}/load")
        resp.raise_for_status()
        resp_data = resp.json()
        return {
            "total_load_w": resp_data["totalPower"],
            "load_percent": resp_data["loadPercent"],
            "phase_loads": resp_data.get("phases", []),
        }

    def check_environmental_limits(self, rack_id):
        sensors = self.get_rack_sensors(rack_id)
        alarms = []
        for sensor in sensors:
            if sensor["type"] == "temperature":
                if sensor["value"] > 27:  # ASHRAE max recommended
                    alarms.append(f"High temp: {sensor['value']}°C at {sensor['location']}")
            elif sensor["type"] == "humidity":
                if sensor["value"] > 80:
                    alarms.append(f"High humidity: {sensor['value']}% at {sensor['location']}")
                elif sensor["value"] < 20:
                    alarms.append(f"Low humidity: {sensor['value']}% at {sensor['location']}")
        return alarms

    def monitor_all_racks(self, rack_ids, interval_s=60):
        """Continuous monitoring loop."""
        while True:
            for rack_id in rack_ids:
                alarms = self.check_environmental_limits(rack_id)
                for alarm in alarms:
                    print(f"[{datetime.utcnow().isoformat()}] ALERT: {alarm}")
            time.sleep(interval_s)

Step 5: Environmental Monitoring Configuration

# monitoring/datacenter-monitoring.yaml
sensor_thresholds:
  temperature:
    warning_c: 27    # ASHRAE recommended max inlet temp
    critical_c: 32   # ASHRAE allowable max inlet temp
    min_c: 18        # Prevent condensation
  humidity:
    warning_percent: 60
    critical_percent: 80
    min_percent: 20
  airflow:
    min_cfm_per_kw: 160
  differential_pressure:
    min_pa: 5        # Underfloor positive pressure

alert_escalation:
  temp_warning:
    - notify: "Datacenter Team (Slack)"
    - wait: 5m
    - notify: "Facilities Manager (PagerDuty)"
  temp_critical:
    - notify: "Datacenter Team (PagerDuty)"
    - notify: "Facilities Manager (Phone)"
    - action: "Initiate emergency cooling procedures"
  power_anomaly:
    - notify: "Electrical Team (PagerDuty)"
    - action: "Check UPS status, initiate generator test"

Step 6: ASHRAE Environmental Guidelines

ClassDry Bulb TempHumidity RangeMax Dew PointBest For
A115-32°C20-80%17°CEnterprise servers, storage
A210-35°C20-80%21°CVolume servers, storage
A35-40°C8-85%24°CIT equipment with extended range
A45-45°C8-90%24°CSpecialized hardware

Step 7: Server Provisioning Automation

# automation/provision_server.sh
#!/bin/bash
# Automated server provisioning with BMC/iLO/iDRAC

SERVER_IP="$1"
BMC_USER="$2"
BMC_PASS="$3"
ISO_PATH="$4"

# Power on and set boot device
ipmitool -I lanplus \
  -H "$SERVER_IP" \
  -U "$BMC_USER" \
  -P "$BMC_PASS" \
  chassis bootdev cdrom

# Mount virtual media
ipmitool -I lanplus \
  -H "$SERVER_IP" \
  -U "$BMC_USER" \
  -P "$BMC_PASS" \
  vm cdrom insert "$ISO_PATH"

# Power cycle
ipmitool -I lanplus \
  -H "$SERVER_IP" \
  -U "$BMC_USER" \
  -P "$BMC_PASS" \
  chassis power reset

# Wait for PXE/installer to boot
echo "Server $SERVER_IP provisioning started. Monitor via BMC web interface."

Step 8: Network Topology — Leaf-Spine

# network/leaf-spine.yaml
topology: leaf-spine
leaf_switches: 4
spine_switches: 2
over_subscription: 3:1

leaf:
  model: "Arista 7280SR-48C6"
  ports:
    server_ports: 48  # 25G SFP28
    spine_uplinks: 6  # 100G QSFP28
  features:
    - MLAG (multi-chassis link aggregation)
    - VXLAN termination
    - sFlow sampling

spine:
  model: "Arista 7300XP-48Y8C"
  ports:
    leaf_ports: 48  # 100G QSFP28
  features:
    - ECMP (equal-cost multipath)
    - EVPN control plane
    - BGP unnumbered

cabling:
  leaf_to_spine: "OS2 singlemode, LC connectors"
  server_to_leaf: "OM4 multimode, LC duplex or CAT6A copper"
  cross_connect: "OS2 singlemode, MPO-12 trunk cables"

monitoring:
  - "Interface utilization > 70% triggers capacity alert"
  - "Packet drop rate > 0.1% triggers investigation"
  - "sFlow data streamed to analytics pipeline"

Step 9: DCIM Tool Configuration — netbox

# dcim/netbox_sync.py
"""Sync server inventory to Netbox DCIM."""
import pynetbox
import json

NETBOX_URL = "https://netbox.example.com"
NETBOX_TOKEN = "your-api-token"

nb = pynetbox.api(NETBOX_URL, token=NETBOX_TOKEN)

def register_server(hostname, serial, rack_id, position, role="server"):
    """Register a server in Netbox."""
    device = nb.dcim.devices.create(
        name=hostname,
        device_type={"id": get_device_type_id("R6525")},
        device_role={"id": get_role_id(role)},
        site={"id": get_site_id("dc-1")},
        rack={"id": rack_id},
        position=position,
        face="front",
        status="active",
        serial=serial,
    )
    return device

def get_device_type_id(model_name):
    types = nb.dcim.device_types.filter(model=model_name)
    return types[0].id if types else None

def get_role_id(role_name):
    roles = nb.dcim.device_roles.filter(name=role_name)
    return roles[0].id if roles else None

def get_site_id(site_name):
    sites = nb.dcim.sites.filter(name=site_name)
    return sites[0].id if sites else None

def audit_power_connections():
    """Report all PDU port utilization."""
    power_feeds = nb.dcim.power_feeds.all()
    for feed in power_feeds:
        outlets = nb.dcim.power_outlets.filter(device_id=feed.device.id)
        connected = sum(1 for o in outlets if o.cable)
        total = len(outlets)
        print(f"{feed.device.name}: {connected}/{total} outlets used")

Step 10: Generator and UPS Test Automation

# maintenance/monthly_generator_test.sh
#!/bin/bash
# Monthly generator load bank test script

echo "=== Generator Monthly Load Test ==="
date -u

# Step 1: Verify fuel level
echo "Fuel level: $(check_fuel_level) gallons (min 75%)"

# Step 2: Start generator in test mode
echo "Starting generator in test mode..."
ipmitool dcmi power_reading | grep "System Power"

# Step 3: Transfer critical load to generator
echo "Transferring UPS input to generator..."
timeout 30 ups-monitor --transfer-to-generator

# Step 4: Monitor for 15 minutes
echo "Monitoring generator output..."
for i in $(seq 1 15); do
  read voltage frequency phase_balance <<< $(generator_metrics)
  echo "Minute $i: ${voltage}V ${frequency}Hz balance:${phase_balance}%"
  sleep 60
done

# Step 5: Transfer back to mains
echo "Transferring back to utility power..."
ups-monitor --transfer-to-utility

# Step 6: Cooldown
echo "Generator cooldown period: 5 minutes..."
sleep 300
echo "Stopping generator..."

echo "=== Test Complete ==="

Tool Comparison: DCIM Platforms

FeatureNetboxDevice42Sunbird dcTrackOpenDCIM
Open sourceYes (Apache 2.0)NoNoYes (GPL)
Rack visualizationYes (2D)Yes (2D/3D)Yes (3D)Yes (2D)
Power trackingYesYesYesYes
Cable managementYesYesYesYes
APIREST + GraphQLRESTRESTREST
Auto-discoveryPluginsYes (agent)Yes (agent)Limited
IPAMYesYesNoNo
Change managementYes (webhook)YesYesNo
PricingFree$$$$Free
Best forOSS-first teamsEnterpriseFacilities teamsBudget-constrained

Rack Density Planning Guide

Density LevelkW/RackCooling RequiredRack TypeTypical Use
Low2-5 kWRoom CRACStandard 42UWeb servers, network gear
Medium5-10 kWRow-basedStandard 42UEnterprise apps, databases
High10-20 kWRow/Rack-basedDeep (48U)Virtualization clusters
Very High20-40 kWRear door HXDeep + wideGPU servers, AI training
Extreme40-100+ kWLiquid coolingCustomHPC, ASIC miners

Security Considerations

  • BMC/iLO/iDRAC ports must be on isolated management VLAN with strict ACLs
  • Default credentials on PDU/UPS/BMC must be changed before deployment
  • SNMP v3 with authentication and encryption for all DCIM polling
  • Physical security: biometric + badge access logged and audited monthly
  • Camera coverage: all rack aisles, entry points, and shipping/receiving
  • Visitor logs: all non-employees sign in/out with escort tracking
  • Rack locks: all racks locked; keys managed via key control system
  • Network taps: no unauthorized taps on structured cabling
  • Remote hands: always supervised by staff; video recorded
  • Decommissioning: drives shredded or degaussed; certificates of destruction maintained
  • Environmental alarms: alert on door open events after hours

Production Considerations

  • PUE should be < 1.6 for air-cooled DCs; < 1.2 for liquid-cooled
  • Test generator and UPS monthly under load with full run-down test annually
  • Maintain cable management to preserve airflow and reduce cooling costs
  • Redundant cooling paths: never route both CRAC units through same pipe
  • Power monitoring per PDU phase prevents unbalanced load conditions
  • Floor loading: verify slab rating (usually 500-1000 kg/m²) before deploying heavy racks
  • Seismic bracing in earthquake-prone regions on all racks and overhead cable trays
  • FM-200/Novec fire suppression tested per NFPA 75 standards annually
  • Maintain spares inventory: PSU, fan, HDD/SSD, SFP+, cable types
  • Document every circuit breaker panel with labels matching DCIM

Anti-Patterns

Anti-Pattern 1: Hot/Cold Aisle Mismanagement

Blocking hot aisle containment or mixing hot and cold air. Proper containment can reduce cooling costs by 20-40%.

Anti-Pattern 2: Over-Subscribing Power Circuits

Plugging more equipment into a PDU than its rated capacity (e.g., 24A on a 20A circuit). Always leave 20% headroom.

Anti-Pattern 3: Ignoring Rack Weight Limits

Filling racks with heavy UPS/gpu servers without checking floor load rating. Server racks can weigh > 1000kg fully loaded.

Anti-Pattern 4: Poor Cable Management

Running cables haphazardly without horizontal/vertical management. Blocks airflow, makes troubleshooting impossible, increases cooling costs.

Anti-Pattern 5: No DCIM

Managing datacenter capacity without DCIM tools. Leads to stranded capacity and inefficiencies.

Anti-Pattern 6: Single Points of Failure in Cooling

Running both CRAC units on the same electrical circuit or same chiller loop. Route redundant cooling from independent sources.

Anti-Pattern 7: No Environmental Monitoring

Only monitoring at room level instead of at rack intake. Rack-level monitoring catches hot spots before they cause failures.

Rules & Constraints

  • Maintain hot aisle / cold aisle configuration at all times.
  • Leave 20% headroom on all power circuits.
  • All cabling must be labeled per TIA-606-B.
  • Environmental monitoring (temp/humidity/power) on every rack.
  • PUE should be < 1.6 for air-cooled DCs.
  • Test generator and UPS monthly under load.
  • Maintain cable management to preserve airflow.
  • SNMP v3 required on all managed infrastructure.
  • Rack weight must not exceed floor load rating.
  • BMC ports restricted to management VLAN only.

References

  • references/cabling.md
  • references/datacenter-advanced.md
  • references/datacenter-capacity-planning.md
  • references/datacenter-fundamentals.md
  • references/datacenter-networking-storage.md
  • references/dcim.md
  • references/rack-power-cooling.md
  • references/tier-classification.md
  • references/ashrae-guidelines.md

Handoff

Next: network-infrastructure — datacenter network architecture.