L’interface est localisée ; les présentations et documents des Skills sont traduits automatiquement par IA dans votre langue. Le code, les commandes, chemins et termes techniques restent en version originale, et le document de l’auteur fait foi.
Explorer les Skills
Productivité · SKILL.md

isa-standards

isa-standards

ISA-5.1 tag naming, ISA-88 batch control, ISA-95 enterprise integration, ISA-18.2 alarm management, and ISA-101 HMI standards reference. Use when working with instrument tags, naming conventions, or plant hierarchy.

Independent GitHub snapshot · Automated classification · Original documentation governs

Documentation de la Skill

GitHub

name: isa-standards description: ISA-5.1 tag naming, ISA-88 batch control, ISA-95 enterprise integration, ISA-18.2 alarm management, and ISA-101 HMI standards reference. Use when working with instrument tags, naming conventions, or plant hierarchy. user-invocable: false

ISA Standards Reference for Industrial Automation

ISA-5.1: Instrumentation Symbols and Identification

Tag Number Structure

[Area].[Functional ID].[Loop Number][Suffix]

Functional ID = [First Letter: measured variable] + [Succeeding Letters: function/modifier]

Examples from project:
  11301.PDI.076A   = Area 11301, Pressure Differential Indicator, loop 076, suffix A
  11301.SALL.020A  = Area 11301, Speed Alarm Low-Low, loop 020, suffix A
  11301.FIC.056A   = Area 11301, Flow Indicating Controller, loop 056, suffix A
  11301.CLWW.1A1   = Area 11301, Conveyor (equipment tag), unit 1A1

First Letter (Measured/Initiating Variable)

LetterVariableAs Succeeding Letter
AAnalysis (pH, O2, conductivity)Alarm
BBurner, CombustionUser's choice
CUser's ChoiceControl
DUser's ChoiceDifferential
EVoltage (EMF)Sensor/Element
FFlow RateRatio/Fraction
GUser's ChoiceGlass/Gauge
HHand (Manual)High
ICurrent (Electrical)Indicate
JPowerScan
KTime, ScheduleTime Rate of Change
LLevelLight/Low
MUser's ChoiceMiddle/Intermediate
NUser's ChoiceUser's choice
OUser's ChoiceOrifice/Restriction
PPressure, VacuumPoint (test)
QQuantityTotalize/Integrate
RRadiationRecord
SSpeed, FrequencySwitch/Safety
TTemperatureTransmit
UMultivariableMultifunction
VVibration, Mechanical AnalysisValve/Damper
WWeight, ForceWell/Probe
XUnclassifiedUnclassified
YEvent, State, PresenceRelay/Compute
ZPosition, DimensionActuator/Driver

Common Tag Combinations

Flow: FE (element), FT (transmitter), FI (indicator), FIC (indicating controller), FCV (control valve), FAH (alarm high), FAL (alarm low), FAHH (alarm high-high), FALL (alarm low-low), FSH (switch high), FSL (switch low), FQI (quantity indicator/totalizer), FR (recorder)

Level: LT, LI, LIC, LCV, LAH, LAL, LAHH, LALL, LSH, LSL, LSHH, LSLL, LG (gauge glass)

Pressure: PT, PI, PIC, PCV, PAH, PAL, PAHH, PALL, PDI (differential indicator), PDIC, PDT, PSH, PSL, PSV (safety valve), PG (gauge)

Temperature: TE (element), TT, TI, TIC, TCV, TAH, TAL, TSH, TSL, TR (recorder), TW (thermowell)

Position/Valve: ZT (position transmitter), ZI, ZIC, ZAH (open alarm), ZAL (closed alarm), ZSH (open switch), ZSL (closed switch), ZSHH, ZSLL

Speed: ST, SI, SIC, SAH, SAL, SAHH, SALL

Current (Electrical): II (current indicator), IIC (current indicating controller), IAH, IAHH

Vibration: VI (vibration indicator), VAH, VAHH

Equipment Tags (Non-ISA, Plant-Specific)

CodeEquipment TypeExample
KKiln/Equipment11301.K.9
NPump11301.N.3A
FFeeder11301.F.4
WGWeighing belt11301.WG.8
SRScreen/Separator11301.SR.9A
CL/CLWWConveyor (weigh)11301.CLWW.1A1
KCCrusher11301.KC.F.4
ELElevator11301.EL.AA
ZSilo/Storage11301.Z.2A

Tag Naming Variations by Region/Vendor

ConventionFormatExample
ISA PureFIC-101AAmerican standard
European (this project)11301.FIC.101AArea.Function.LoopSuffix
Siemens/KKS+FIC101A=German power plant standard
DeltaV pathFIC-101A/PVWith parameter path
HoneywellFIC101A.PVWith point parameter

ISA-88: Batch Control (S88)

Physical Model Hierarchy

Enterprise
  +-- Site
       +-- Area
            +-- Process Cell
                 +-- Unit
                      +-- Equipment Module (EM)
                           +-- Control Module (CM)

Mapping to DCS Engineering

ISA-88 ConceptDCS ImplementationExample
Control ModuleFunction block instanceMotor block, valve block, PID loop
Equipment ModuleSequence/SFCReactor filling sequence
UnitProcess unit with sequencesReactor R-101
Process CellGroup of unitsProduction Line A

Control Module Types (Standard Templates)

  • Motor CM: Start/Stop, feedback, interlock, mode selection
  • On/Off Valve CM: Open/Close, position feedback, interlock
  • Modulating Valve CM: Analog output, position feedback, PID output
  • PID Loop CM: AI input, PID algorithm, AO output
  • Analog Input CM: Scaling, filtering, alarm limits
  • Digital Input CM: State detection, alarm on state

ISA-95: Enterprise-Control Integration

Equipment Hierarchy (extends ISA-88 upward)

Enterprise > Site > Area > Work Center > Work Unit

Relevance to Tag Naming

Tags should encode the hierarchy. Example: 11301.FIC.056A

  • 11301 = Area identifier (maps to ISA-95 Area)
  • FIC = Function (ISA-5.1)
  • 056 = Loop number (unique within area)
  • A = Suffix (parallel instance)

ISA-18.2: Alarm Management

Alarm Priority Distribution (Guideline)

PriorityPercentageResponse Time
Critical (1)~5%Immediate
High (2)~15%< 5 minutes
Medium (3)~30%< 30 minutes
Low (4)~50%Next round

Alarm Tag Properties for Bulk Engineering

Each alarm tag requires: Priority, Setpoint (limit), Deadband, On-delay, Off-delay, Alarm class (Process/Safety/Equipment), Shelving capability.

Naming Convention for Alarms

{Area}.{Variable}{AlarmType}.{Loop}{Suffix}
  PAH  = Pressure Alarm High
  PAHH = Pressure Alarm High-High
  PAL  = Pressure Alarm Low
  PALL = Pressure Alarm Low-Low

In Freelance EAM: XA1 = primary alarm, XA2 = secondary alarm

ISA-101: Human Machine Interfaces

Display Hierarchy

LevelNameContentQuantity
1Plant OverviewEntire plant, KPIs1-3
2Area OverviewOne process area5-20
3Unit DetailOne unit operation20-100
4Faceplate/DetailOne control loopAuto-generated

High-Performance HMI Principles

  • Gray backgrounds (not black)
  • Analog representations (bar graphs, sparklines, not just numbers)
  • Minimal animation (no rotating equipment, no flowing pipes)
  • Color reserved for abnormal states (alarms, deviations)
  • Consistent navigation (plant hierarchy)
  • Situational awareness focus
Skills enregistrées